Disconnect Switch DS -10/630

The disconnect switch DS-10/630 is designed for repeated switching without load of sections of three-phase current circuits with a voltage of 6 (10) kV, frequency of 50 Hz, and grounding of disconnected sections using grounding knives.
The disconnect switch is installed in:
- complete transformer substations;
- one-sided serviceable assembly chamber;
- complete distribution device.
Disconnecting Switch DS-10/630 is a three-pole switch of the vertical-break type, consisting of:
- frame with insulators;
- current-carrying contacts;
- one or two grounding knives;
- manual drive.
The stationary contacts from the copper busbar (plug connection and non-plug hinge connection) are mounted on insulators installed on the switch frame. Also, the frame is equipped with a drive shaft, grounding knife, and other switch components.
The movable contact knives are connected to the stationary contacts through a hinge connection.
Technical data of the Disconnecting Switch DS-10/630 disconnect switch:
Nominal voltage, 6...10 kV
Maximum operating voltage, 12 kV
Nominal current, 630 A
Thermal stability current, 20 kA
Electrodynamic stability current, 51 kA
Thermal stability current duration, 3 s
Maximum effort applied to the drive, not more than 250 N
Phase-to-phase distance, 200 (250) mm
dimensions for I, II - 650 x 410 x 250(430), 19.5 kg
dimensions for III - 650 x 500 x 250(430), 24 kg
Load Break Switch LBS-10/630

The LBS-10/630 load break switches with grounding knives are designed for switching under load of sections of three-phase current circuits with a voltage of 6 (10) kV, frequency of 50 Hz, and grounding of disconnected sections using knives.
The load break switch is installed in:
- Complete Transformer Substation;
- Prefabricated chamber of unilateral service;
- Pole-mounted Outdoor Device.
LBS switches are equipped with an auto-gas arc extinguishing device. The arc is extinguished by the gas flow released from the walls of the arc extinguishing chamber when the arc affects them.
Control is carried out by a separate drive associated with the load break switch, which is mounted at the installation site of the switch. Drive type: spring (manual) or electric drive.
Technical characteristics:
Nominal voltage, 10 kV
Nominal current, 630 A
Nominal initial value of the periodic component of the short-circuit current, 20 kA
Weight with grounding knives (with grounding knives and fuses), 52 (87) kg
Dimensions (dimensions with fuses), width x height x depth, 625x594x495 (625x1131x495) mm
Outdoor Double-Column Line Disconnector-10/630 Disconnect Switch with PR-01 Drive

The three-pole disconnect switches Outdoor Double-Column Line Disconnector 10/630 are designed for universal use in high-voltage networks and on open substations of AC frequency of 50 Hz network sectionalization and disconnection of consumers from the network without load, to create a visible gap in the line.
Technical data of the Outdoor Double-Column Line Disconnector10/630 disconnect switch:
Nominal voltage, 6-10 kV
Maximum operating voltage, 12 kV
Nominal current, 630 A
Weight, not more than 77 kg
Dimensions Outdoor Double-Column Line Disconnector 10/630, 1200 × 470 × 385 mm
Dimensions Outdoor Double-Column Line Disconnector 10/400, 875 x 805 x 495 mm